Part 1 – General – VB250
11 mil.
1.1 Section Includes
A. Products supplied under this section
1. Vapor Barrier and seam tape for installation under
concrete slab
1.2 Related Section
A.
Section 07260 –
Under Slab Vapor Retarder
B.
Section 03300 –
Cast-in-place Structural Concrete
1.3 References
A.
American
Concrete Institute (ACI)
1. ACI 302.1 R – 96 – Vapor retarder / barrier membrane
is greater than or equal to 10 mils in thickness
B.
American
Society for Testing and Materials (ASTM)
1. ASTM
E 96 – Water vapor transmission of materials
2. ASTM
E 1745 – Water vapor retarder used in contact with soil or
granular fill under concrete slabs
3. ASTM
E 154 – Water vapor retarder used in contact with earth
under concrete slabs, walls, or ground cover
4. ASTM
E 1643 – Installation of water vapor retarder used in
contact with earth under concrete slabs
1.4 Submittals
A.
Submit
manufacturers product data and installation instruction
B.
Submit
laboratory test results showing compliance with ACI and ASTM
standards
C.
Submit
manufacturers product samples
Part 2 – Products – VB250 11 mil.
2.1 Manufacturer
A. Barrier-Bac, 9 Peach Tree Hill Road, Livingston, NJ 07039
973-994-8035 * Fax: 973-740-8244
2.2 Materials
A. High density polyethylene vapor barrier
1. Description:
Three layer coextruded biaxially oriented polyethylene
membrane
2. Water
vapor transmission ASTM E – 96 less than or equal to 0.009 g
/ m2
*h
3. Tensile
strength ASTM D – 882 minimum 48 lbs / in
4. Permeance
ASTM E – 96 less than or equal to .012 perms
5.
Puncture resistance ASTM D – 1709 greater than or equal
to 2408 grams
2.3 Accessories
A.
Seam tape
1. 8 mil PVC tape with rubber/resin adhesive. Tensile
strength not
less than 22 lbs./inch minimum per ASTM D 882.
Minimum width of 4 inches.
B. Pipe
Boots 1. Follow manufacturers instruction to construct pipe
boots
with vapor barrier membrane and seam tape